Perchloric acid fume hood

Perchloric Acid Fume Hoods are designed particularly for the process involving the use of perchloric acid. The fume hood system has entire work surface, an inner water wash down system and built in drain trough provided for detailed cleaning of the hood interior. Perchloric acid is incompatible, and might react vigorously, with a variety of organic, flammable and combustive materials, such as wood, rubber, paper and greases. So, it’s recommended only to use perchloric acid only. The formation of perchlorate may be a significant concern when using and storing perchloric acid. Perchlorate salts, also known as perchloric acid crystals, are immensely shock-sensitive and unstable, having a dangerous of explosion when unprotected to shocks and vibrations. Perchlorate salts are formed when perchloric is heated and as a result the vapours are allowed to condense onto a surface and dry. Perchlorates salt which could accumulate within the hood and ductwork system and become explosive. It requires wash down features to stop perchlorates salt buildup in hood and ductwork. The spray nozzle system is installed to allow complete flushing of all duct, hoodsurfaces, stack and exhaust fan.

Ductwork from perchloric acid hoods and exhaust systems should take the shortest path to the outside and should not mix with the other exhaust systems. The interior baffles can be removed for cleaning to stop the dangerous build-up of perchlorates. A visual check of the fume hood should be performed whenever the hood is used to make sure that the wash-down system is functioning correctly and air is being pulled into the hood. Regular cleaning of the perchloric acid fume hood is vital to make sure that build-ups of dust or material which can contain perchlorate salts don’t occur.

Technical specifications

MOC

CRCA 18G Epoxy powder coated

Stand

MS pipe, 18 G powder coated

Working table top

MS powder coated sheet covered with PP sheet

 

Exhaust system

Motor Blower assembly covered with GI sheet

Sash/ Door

Vertical folding type

Air velocity

0.5 m/s

Noise Level

65 dBA

Glass window

Two layer toughen glass

5 mm thickness

Adjustable height

Motor control

Make up air

Air needed to replace the air exhausted from a room by the fume hood and other ventilation devices

Face velocity

The velocity of the air passing through the work opening of the fume hood measured in the plane of the sash. Measured in feet per minute (fpm), or liters per minute

Electrical fittings

Electrical sockets and MCB switch

Illumination

Fluorescent lamp or UV lamp

Optional accessories

HEPA Filter
Caster wheels
Horizontal sash
SS 314 / SS 316 MOC
Temperature indicator

Face Velocity Meter
Airflow Indicator
Audio / Visual alarm

Power supply

220 / 230 V

 

Dimensions

 
 

Model No.

CFM                         @29″

CFM                   @18″

Super structure

Worktop

Hood opening

 

W (mm)

H (mm)

D (mm)

W (mm)

H (mm)

D (mm)

W (mm)

H (mm)

 

 DPFH-90

567

354

915

1425

845

915

40

762

660

740

 

 DPFH-120

833

521

1220

1425

845

1220

40

762

965

740

 

 DPFH-150

1100

688

1525

1425

845

1525

40

762

1270

740

 

 DPFH-180

1367

854

1830

1425

845

1830

40

762

1575

740

 

 DPFH-240

1900

1188

2440

1425

845

2440

40

762

2185

740

 

  Accessories

  • Fume hood base cabinet
  • Blower
  • Ceiling enclosures
  • Water faucet
  • Electrical accessories

Features

  • Powder coat finish
  • Manual washdown
  • Built in drain trough
  • Stainlesssteel sash
  • Stainless steel airfoil
  • SS 316 one piece integral work surface and liner

Optional Accessories

  • Apparatus rack
  • Air flow monitors